Jotul GF 3 BV User Manual

Page 7

Advertising
background image

VENTING REQUIREMENTS:

The Allagash is specifically designed to operate

using 4” Type B vent pipe components or a Listed

Flexible gas liner.

FOLLOW THE GUIDELINES LISTED

BELOW FOR THE PROPER VENTING OF

THE ALLAGASH B-VENT STOVE!

• All venting components must be installed in

accordance with the terms of their listing and

manufacturer’s instructions.

• The minimum height of a vertically terminated

system shall be no less than 7', and the

maximum height shall be no more than 35'.

See diagrams page 9.

• With steep roofs, nearby trees, and in

predominant windy conditions, poor draft or

down draft conditions can occur. In these cases,

increasing the height of the vent or high wind

termination caps may improve the situation.

• ELBOWS: If an offset or elbow is necessary

in the vertical rise, it is important to support

the vent pipe every three feet, to avoid excessive

stress on the offsets.

• Whenever possible use 45° elbows opposed to

90° elbows. This offers less restrictions for the

flow of flue gases.

Maximum number of 90° elbows = three

Maximum number of 45° elbows = four

• TOTAL MAXIMUM HORIZONTAL

RUN ANYWHERE IN THE VENTING

CONFIGURATION IS 4 FEET. The distance

between any 45° elbows is considered a

horizontal run. See diagrams page 9.

•

Any Type B vent passing through a roof must

have a flashing, storm collar, thimble and a

Type B cap is required. See diagrams page 9.

•

Venting on the Allagash CANNOT be less than

4” in diameter or greater than 4” in diameter.

• Any

UNUSED

flue or masonry enclosure can be

used as a passage way for venting the Allagash:

PROVIDED the flue is relined using Type B

4” vent or Listed Flexible Gas Liner.

• The remaining space around the liner in a

masonry or zero-clearance flue CANNOT be

used to vent any other appliance.

• When terminating through the roof refer to the

Gas Vent Rule for proper vent termination

height. See Figure 1.

•

NO venting can terminate horizontally or

below roof eaves.

•

Passage through combustibles (walls, ceilings)

must be with Type B venting and must

maintain listed clearances.

•

It is recommended that any horizontal runs

have an upward slope of 1/4” per foot toward

the termination cap.

•

When venting through a thimble into a

masonry flue any venting exposed in the room

must be Type B venting.

•

Listed Flexible Gas Liners may not be exposed

in any living space.

7

Figure 1

Advertising