The appliance must be isolated from the gas supply

line by closing its individual manual gas shut-off

valve (gas cock) during any pressure testing of

the gas supply piping system that is equal to or

exceeds pressures of 1/2 psig (3.5kPa).

NECESSARY INLET GAS PRESSURES

(inches water column)

MIN

MAX

NATURAL GAS

5.0 WC

7.0 WC

PROPANE

11.0 WC 13.5 WC

NECESSARY MANIFOLD PRESSURES

(inches water column)

MIN MAX

NATURAL GAS

2.2 WC

3.5 WC

PROPANE

6.5 WC

10.0 WC

ALWAYS TEST PRESSURES WITH VALVE

CONTROL KNOB SET ON HIGH

Symptons of incorrect gas pressure include:

Insufficient gas pressure:

• Small pilot flame which can result in

insufficient millivolts.

• Little variation in flame picture between HI

and LO settings.

• Insufficient gas to support more than one

appliance causing nusance outages or gas

surges.

Excessive gas pressure:

• Permanent damage to valve causing complete

appliance shut down.

• Too large a pilot flame resulting in over heating

of the power generator causing shut down.

• Sooting due to impingement and/or incorrect

fuel to air mix.

HIGH ALTITUDE INSTALLATIONS:

When installing the Allagash in high altitude

(above 2000') situations it becomes necessary to

compensate for the thinner air (less volume of

air per cubic foot). Higher altitudes effect the

atmospheric pressure and heat value of gaseous

fuels. The lower oxygen content in the air and

the lower gas viscosity require the use of a

different orifice to achieve efficient, clean

combustion at the burner tube.

In the U.S.

THE DERATING KIT MUST BE INSTALLED BY

AN AUTHORIZED SERVICE TECHNICIAN IN

ACCORDANCE WITH THE MANUFACTURER’S

INSTRUCTIONS AND ALL CODES AND

REQUIREMENTS OF THE AUTHORITY HAVING

JURISDICTION. THE INFORMATION STICKER

MUST BE FILLED OUT BY THE INSTALLER AND

ADHERED TO THE APPLIANCE AT THE TIME

OF THE CONVERSION. THE QUALIFIED SERVICE

AGENCY PERFORMING THIS WORK ASSUMES

RESPONSIBILITY FOR THIS DERATING.

In Canada

THIS UNIT HAS BEEN TESTED FOR

INSTALLATION AT HIGH ALTITUDES IN

ACCORDANCE WITH CANADIAN TEST

STANDARD CAN/CGA-2.17.THE DERATING

SHALL BE CARRIED OUT IN ACCORDANCE

WITH THE REQUIREMENTS OF THE

PROVINCIAL

AUTHORITIES

HAVING

JURISDICTION AND IN ACCORDANCE WITH

THE REQUIREMENTS OF THE CAN1-B-149.1

AND .2 INSTALLATION CODE.

For installations from 2000ft.(610m) to

4500ft.(1370m) the orifice size for:

natural gas is a #42

propane gas is a #55

SEE THE HIGH ALTITUDE ORIFICE CHART

on page 14.

For high altitude installations consult the local

gas distributor or the authority having jurisdiction

for proper rating methods. If the installer must

convert the unit to adjust for varying altitudes,

the information sticker must be filled out by the

installer and adhered to the appliance at the time

of the conversion. See Figure 6.