• When decorative 6” pipe is installed to cover

the venting any Listed Flexible Gas liner must

be connected directly to the stove’s draft hood.

• Use of single wall connector pipe as a vent is

prohibited for use with the Allagash B-Vent stove.

• A firestop is required at every floor.

• Any venting that is exposed above the first

floor, regardless of attic space or living space,

must be enclosed. Always maintain the

required clearance from all sides of the vertical

vent system according to manufacture.

• Installation of any components not

manufactured or approved by Jøtul or failure

to meet all clearance requirements will void

all warranties and could result in property

damage, bodily injury, or serious fire.

• Never modify any venting component, or use

any damaged venting product.

• THE GAS APPLIANCE AND VENT

SYSTEM MUST BE VENTED DIRECTLY

TO THE OUTSIDE OF THE BUILDING,

AND NEVER ATTACHED TO A

CHIMNEY SERVING A SOLID FUEL OR

GAS BURNING APPLIANCES.

• BE SURE TO MAINTAIN THE PROPER

CLEARANCES TO COMBUSTIBLES AS

DEFINED IN THIS MANUAL AND IN

THE INSTRUCTIONS PROVIDED WITH

EACH VENTING COMPONENT.

• When installing at an altitude above 2000’ the

minimum vertical rise becomes 12’ from the

draft hood.

•

If more than two feet of venting is exposed to

the outside, the entire exterior vent system

must be enclosed in an insulated chase system.

8

Listed termination

cap required

Storm collar

required

Recommended

damper sealing plate

to seal flue chamber

to prevent heat loss

Allagash B-Vent gas

stove

Always maintain

the proper

clearance to mantel

and trim

Allagash B-Vent gas stove vented into a

masonry or prefabricated fireplace.

Maximum

offset is 4’

Type B vent or

Listed Flexible

Gas Liner. On

outside chimneys

Jøtul recommends

the use of Type B

vent to help keep

the gases warm and

rising.

max. height 35’

min. height 7’

Top sealing

achor plate

WARNING

:

FAILURE

TO

POSITION

THE

PARTS

IN

ACCORDANCE

WITH

THIS

DIAGRAM

OR

FAILURE

TO

USE

ONLY

PARTS

SPECIFICALLY

APPROVED

WITH

THIS

APPLIANCE

MAY

RESULT

IN

PROPERTY

DAMAGE

OR

PERSONAL

INJURY

.