2. SPECIFICATIONS

MODEL No.

Indoor Unit

KS2462R

Outdoor Unit

C2462R

POWER SOURCE

230 - 208 V / 1 Phase / 60 Hz

PERFORMANCE

Cooling

Capacity

kW

7.912

BTU / h

BTU / Wh

27,000

Air circulation (Hi)

Cu.ft. / min.

559

Moisture removal (High)

Pints / h

6.5

7.619

26,000

519

6.4

ELECTRICAL RATINGS

Voltage rating

VAC
VAC

230

Available voltage range

187 – 253

Running amperes*

A

10.2

Max. running amperes**

A

12.5

Power input

W

2,240

Power factor

%

95.5

S.E.E.R

13.0

Max. starting amperes

A

61

208

10.9
13.5

2,200

97.0

13.0

61

FEATURES

Controls

Microprocessor

Timer

ON/OFF 24-hours & Program

Fan speed Indoor / Outdoor

3 and Automatic control / 2 (Auto)

Air deflection

Horizontal / Vertical

– / Automatic

Air filter

Washable, easy access

Remote controller (Accessory)

RCS - 1PS4U - G

Refrigerant control

Capillary tube

Refrigerant tubing connections

Flare type

Compressor

Scroll

Operation sound

Indoor - Hi/Me/Lo

dB - A

48 / 42 / 38

Outdoor - Hi

dB - A

55

REFRIGERANT TUBING

Limit of tubing length

ft. (m)
ft. (m)
ft. (m)

in. (mm)
in. (mm)

132 ( 40 )

Limit of tubing length at shipment

23 ( 7 )

50 ( 15 )

Limit of elevation difference
between the two units
Refrigerant tube

Narrow tube

3 / 8 (9.52)

outer diameter

Wide tube

3 / 4 (19.05)

Refrigerant amount at shipment

lbs. (kg)

R410A - 6.6 (3)

DIMENSIONS & WEIGHT

Indoor unit

Outdoor unit

Unit dimensions

Height

in. (mm)
in. (mm)
in. (mm)
in. (mm)
in. (mm)
in. (mm)

Width
Depth

Package dimensions

Height
Width
Depth

15-31/32

(406)

44-7/8

(1,140)

12-25/32

(325)

48-15/32

(406)

8-31/32

(228)

Net weight

lbs. (kg)
lbs. (kg)

40

(18)

44

(20)

5.7

(0.162)

150

(68)

190

(86.5)

14.1

(0.40)

36-5/8

(930)

37

(940)

13-3/8

(340)

39-3/4

(1,010)

39-3/8

(1,000)

15-3/4

(400)

13

(330)

Shipping weight
Shipping volume

3

cu. ft.(m )

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Cooling:

Rating conditions (*)

: Indoor air temperature 80

°

F DB / 67

°

F WB, Outdoor air temperature 95

°

F DB / 75

°

F WB

Full load conditions (**) : Indoor air temperature 80

°

F DB / 67

°

F WB, Outdoor air temperature 115

°

F DB

1-1 Unit Specifications

Advertising