Service procedures – Sanyo CL2462R User Manual

Page 53

Advertising
background image

– 53 –

SM830092

Fan motor
capacitor

Compressor motor
capacitor

1041_X_S

Multimeter

Fig. 21

3)

Checking the Electrical Parts

1

Power transformer ...........................Indoor unit

*Measure the coil resistance.

• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals

of socket connected to power transformer.

• Secondary 19 V

; Measure the resistance between two BRN lead wires.

2

Power transformer (TR) ................. Outdoor unit

*Measure the coil resistance.

• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals

of socket jointed to power transformer.

• Secondary 19 V

; Measure the resistance between two BRN lead wires.

3

Indoor fan motor (FMI) ............... Indoor unit

*Measure the coil resistance.

• Measure the resistance between each terminal of the socket connected to the

indoor fan motor.

4

Outdoor fan motor (FMO) ........... Outdoor unit

*Measure the coil resistance.

• Measure the resistance in the same manner as explained above 2 .

5

Motor capacitor ............ Both in indoor and outdoor unit

• Remove the lead wires from the

capacitor terminals, and then place a
probe on the capacitor terminals as
shown in Fig. 21. Observe the deflec-
tion of the pointer, setting the resis-
tance measuring range of the multim-
eter to the maximum value.

• The capacitor is “good” if the pointer

bounces to a great extent and then
gradually returns to its original posi-
tion.

The range of deflection and the deflection
time differ according to the capacity of the
capacitor.

NOTE

12. SERVICE PROCEDURES