48

Heating

Room temperature control is obtained by cycling the compressor ON and OFF under control of the room tem-

perature sensor in the remote control unit.

The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the

controller in the indoor unit.

The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5

minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pres-

sure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.

As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor

operation.

Thermo. ON : When the room temperature is below T – 2°F (T°C is set temperature).

Compressor

ON

Thermo. OFF : When the room temperature is equal to or above set temperature T°F.

Compressor

OFF

*1: Refer to "8-6 Cold Draft Prevention".

NOTE

3 minutes

3 minutes

3 minutes

3 minutes

3 minutes

3 minutes

5 minutes

5 minutes

ON

OFF

ON

OFF

Compressor

OFF

ON

OFF

ON

OFF

Outdoor fan

OFF

Set speed

LL

LL

ON

OFF

OFF

OFF

ON

OFF

ON

*1

OFF

OFF

ON

ON ( Reversing cycle )

Thermo.
ON

Thermo.
OFF

Thermo.
ON

Thermo.
OFF

More than

5 minutes

Signal from remote control unit

T

¡

F

T – 2

¡

F

T – 4

¡

F

set temp.

Indoor fan

Standby lamp

Indoor heat exch.
coil temp.

95

¡