Communication wiring, Controller led indicators – Siemens BACnet ATEC 125-5050 User Manual

Page 12

Advertising
background image

Chapter 1 – Product Overview

12
Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Communication Wiring


The controller connects to the field panel by means of a Floor Level Network (FLN)

trunk. Communication wiring connects to the three screw terminals on the controller

labeled “+” (positive), “-“(negative), and “S” (Shield). See the following figure.

Controller LED Indicators

The controller has six Light Emitting Diode (LED) indicators (see the figure

Siemens

BACnet ATEC

).

Controller LEDs.

LED Type

Label

(if present)*

LED

Number

Indication

DO

LED 3 - LED 5

3 - 5

Indicates the ON/OFF status of the DO

associated with it. A glowing LED indicates

that the DO is energized.

Transmit

TX

0

Indicates, when flashing, that the controller is

transmitting information to the field panel.

Receive

RX

1

Indicates, when flashing, that the controller is

receiving information from the field panel.

BST

”Basic Sanity

Test”

BST

2

Indicates, when flashing ON and OFF once

per second, that the controller is functioning

properly.

* Some LED labels and numerals may be hidden by the controller cover.