Chapter 2 – Applications

14
Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Chapter 2 – Applications

Basic Operation

The BACnet ATEC provides Direct Digital Control (DDC) for Variable Air Volume (VAV)

terminal box applications. Temperature control varies with the application. If present,

heating can be provided by hot water, up to three stages of electric reheat, or optional

baseboard radiation.

Sequencing Logic (optional)

This application has the additional capability to sequence the flow and mechanical

heating when heated supply air is available.

Control Temperature Setpoints

The controller maintains a specified temperature setpoint based on Day/Night mode, or

the heating/cooling mode, or the setpoint dial (if used).

Day/Night Mode

The controller maintains the specified day setpoint temperature during daytime hours

and the specified night setpoint at night.

Night Mode Override Switch

If the ROOM TEMPERATURE SENSOR has an override switch, it can be used to

command the controller into day mode for an adjustable period of time. This only

affects a controller in night mode.

Control Loops

Temperature Loop – Heating Loop – Cooling Loop

Maintain temperature setpoint by changing the flow setpoint or modulating the heat

source (valve/electric heat).

Flow Loop

Maintains flow setpoint by modulating the damper actuator.