Siemens BACnet ATEC 125-5050 User Manual

Page 29

Advertising
background image

Chapter 3 – Point Database

29

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Descriptor

Address

1

Application

Description

OFF for 5 minutes, and Stage 3 is OFF.

SWITCH DBAND

90

All

except

2560, 2561, 2597

The temperature range in degrees which is compared to the

difference between CTL TEMP and CTL STPT. The difference

must exceed this value for temperature control mode to

change over. Changeover is also subject to the active

temperature control loop output being below SWITCH LIMIT

(Point 85) and SWITCH TIME being expired.

CTL STPT

{92}

All

except

2597

The actual setpoint value being used as input for the active

temperature control loop.

FLOW STPT

{93}

All

except

2597

The setpoint of the flow control loop.

CAL AIR

{94}

All

YES commands the controller to go through calibration

sequence for the air velocity transducers. YES is also

displayed when the calibration sequence is started

automatically. CAL AIR automatically returns to NO after the

calibration sequence is completed. Valid input: YES or NO.

CAL SETUP

95

All

The configuration setup code for the calibration sequence

options.

CAL TIMER

96

All

Time interval, in hours, between the calibration sequence

initiations if a timed calibration option is selected in CAL

SETUP.

DUCT AREA

97

All

Area, in square feet (square meters), of the duct where the air

velocity sensor is located. This is a calculated value

(calculated by the field panel or computer being used) that

depends on duct shape and size. It is used in calculating all

points in units of CFM, CF, LPS and L.

Valid input: .025 ft2 (.002 m2) through 6.375 ft2 (.5923 m2).

LOOP TIME

98

All

except

2597

The time, in seconds, between control loop calculations.

ERROR STATUS

{99}

2

All

The status code indicating any errors detected during

controller power up. A status of 0 indicates there are no

problems.

UI 1 CFG

102

All

Configuration point for universal input 1 (digital, analog –

thermistor, 0 to 10V or 4 to 20mA).

PERCENT UI1

{103}

All

Universal input 1 when configured as 0 to 10V or 4 to 20 mA.

UI2 CFG

104

All

Configuration point for universal input 2 (digital, analog –

thermistor, 0 to 10V or 4 to 20 mA).

PERCENT UI2

{105}

All

Universal input 2 when configured as 0 to 10V or 4 to 20 mA.

AIR ALTITUDE

106

All

Optional correction factor for flow sensor based on altitude.

TUBE LEN

107

All

Optional correction factor for flow sensor based on tube length

of air tube pickup.

TUBE DIAMETE

108

All

Tube diameter (inside) of air tube pickup.

AUX TEMP UI2

{109}

All

Temperature sensor (when UI 2 is configured for 10K

thermistor).

STAT SUPV

126

All

Room unit configuration point, values are additive.

RM RH

127

All

Room humidity when room unit is provided with humidity

sensing.

1)

Points not listed are not used in this application.

2)

Point numbers that appear in brackets { } may be unbundled at the field panel.

Advertising