Fan operation – Siemens BACnet ATEC 125-5050 User Manual

Page 19

Advertising
background image

Chapter 2 – Applications

19

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Application 2864 VAV Series Fan Powered with Electric Reheat

In Application 2864, the controller modulates the supply air damper of the terminal box

for cooling and controls stages of electric reheat for heating. When in heating, the

terminal box either maintains minimum airflow or modulates the supply air damper.

Application 2864 has a series fan for air circulation. In order for the terminal box to

work properly, the central air-handling unit must provide supply air.
See the following figure.

Fan Operation

CAUTION

On series fan powered terminal boxes, the terminal box fan must be
controlled/interlocked to start either before or at the same time as the central air
handler. Failure to do so may cause the terminal box fan to rotate backwards and
cause consequent damage at start up.


In day mode, the fan is ON all the time. In night mode, the fan cycles on when heating

or cooling is required.

Advertising