Fan operation, Application 2897 slave mode, Using auxiliary points – Siemens BACnet ATEC 125-5050 User Manual

Page 22: Using the controller as a point extension device

Advertising
background image

Chapter 2 – Applications

22
Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Fan Operation


The fan turns on when heating is required.

[insert TEC2567CD]

Application 2897 Slave Mode

Application 2897 is the slave mode application for the BACnet ATEC (see Ordering

Notes [ 9] for product numbers). Slave mode is the default application that comes up

when power is first applied to the controller. Slave mode provides no control. Its

purpose is to allow the operator to perform equipment checkout before a control

application is put into effect and to set some basic controller parameters (CTLR

ADDRESS, APPLICATION, etc.). A controller in default state can also be used as a

point extension device by unbundling spare I/O points at the field panel.

Using Auxiliary Points

It is possible to have extra points available on a BACnet VAV Controller — Electronic

Output in addition to the ones used by the current application that is running in the

controller. If these extra points are to be controlled by a field panel, then they must be

unbundled at the field panel.

Using the Controller as a Point Extension Device

If the controller is only used as a point extension device, with no control application in

affect, its application must be set to slave mode and points must be unbundled at the

field panel. All points must be controlled from the field panel in order to be used.

Advertising