Chapter 2 – Applications

21

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

See the following figure.

Fan Operation


The fan turns on when heating is required.

[insert TEC2566CD]

Application 2867 VAV Parallel Fan Powered with Hot Water Reheat

In Application 2867, the controller modulates the supply air damper of the terminal box

for cooling and modulates a hot water valve for heating. When in heating, the terminal

box either maintains minimum airflow or modulates the supply air damper. Application

2867 has a parallel fan that re-circulates the room air. In order for the terminal box to

work properly, the central air-handling unit must provide supply air.
See the following figure.