Siemens BACnet ATEC 125-5050 User Manual

Page 25

Advertising
background image

Chapter 3 – Point Database

25

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Descriptor

Address

1

Application

Description

controller's Ul 1 input. The controller uses this value to

determine whether it is in heating or cooling mode.

FLOW START

16

All

except

2560, 2561, 2597

Determines how the damper modulation will be sequenced

while in heating mode. When HTG LOOPOUT is above this

value, then FLOW STPT starts to increase.

FLOW END

17

All

except

2560, 2561, 2597

Determines how the damper modulation will be sequenced

while in heating mode. When HTG LOOPOUT is below this

value, then FLOW STPT starts to decrease.

WALL SWITCH

18

All

YES indicates that the controller is to monitor the status of a

wall switch that is connected to UI 2. NO indicates that the

controller will not monitor the status of a wall switch, even if

one is connected. Valid input: YES or NO.

DI OVRD SW

{19}

2

All

Actual indication of the status of the override switch (not

physically available on all temperature sensor models) at the

room temperature sensor. ON indicates that the switch is

being pressed. OFF indicates that the switch is released.

Valid input: ON or OFF.

OVRD TIME

20

All

except

2597

The amount of time in hours that the controller will operate in

day/occupied mode when the override switch is pressed while

the controller is in night/unoccupied mode.

NGT OVRD

{21}

2

All

except

2597

Indicates the mode that the controller is operating in with

respect to the override switch. NIGHT indicates that the switch

has not been pressed and the override timer is not active.

DAY indicates that the switch has been pressed and the

override timer is active. The controller then uses a day mode

temperature setpoint. This point is only in effect when

DAY.NGT indicates night mode.

REHEAT START

22

All

except

2560, 2561, 2597

Determines how the reheat modulation will be sequenced

while in heating mode. When HTG LOOPOUT is above this

value, then the reheat modulates upward.

REHEAT END

23

All

except 2560, 2561,

2597

Determines how the reheat modulation will be sequenced

while in heating mode. When HTG LOOPOUT is below this

value, then the reheat modulates downward.

DIGITAL UI 2

{24}

All

Actual status of a contact connected to the controller at UI 2.

ON indicates that the contact is closed; OFF indicates that the

contact is open. If a wall switch is used, it is connected to UI

2. See WALL SWITCH.

DIGITAL UI 1

{25}

2

All

except

2561

Actual status of a contact connected to the controller UI 1. ON

indicates that the contact is closed; OFF indicates that the

contact is open. When a contact is connected as a digital

input, the analog input is not available. See AUX TEMP.

SERIES ON

26

2564, 2565

When flow rises above this value, the series fan will turn ON.

SERIES OFF

27

2564, 2565

When flow drops below this value and other conditions have

been met, the series fan will turn OFF.

PARALLEL ON

28

2566, 2567

When flow drops below this value and other conditions have

been met, the parallel fan will turn ON.

DAY.NGT

{29}

All

Indicates the mode in which the controller is operating. Day

temperature setpoints will be used in day mode. Night

temperature setpoints will be used in night mode. This point is

normally set by the field panel.

PARALLEL OFF

30

2566,

2567

When flow rises above this value, the parallel fan will turn

OFF.

CLG FLOW MIN

31

All

except 2597

The minimum amount of air in CFM (LPS) to be supplied to

Advertising