Read Device Registers

Action

Result

1. From the Diagnostics page, click Read

Device Registers.

Opens the Read Device Registers page.

2. Enter the device ID, starting register

number, and the number of registers to
read.

Enters the values to begin reading registers for
the specified device.

3. Click Read Holding Registers or Read

Input Registers.

Displays the values for the listed registers.

4. To change how the data is displayed in the

Value column, select Decimal,
Hexadecimal, Binary, or ASCII.

Selects how the data values are displayed.

Table 7:

ETG Read Device Register Settings

Option

Description

Default

Device ID

The address of the device that registers are read.

1

Starting Register

The first register to read.

1000

Number of Registers

The number of registers to read (1 to 10).

10

Register column

Lists the register numbers

Value column

Lists the data stored in a register.

Decimal, Hexadecimal,
Binary, or ASCII options

Select an option to specify how the Value column
data is displayed.

Decimal

Figure 13:

Read Device Registers Page