Setup, Ethernet and tcp/ip settings, En g l is h – Schneider Electric TSXETG100 User Manual

Page 5

Advertising
background image

63230-319-211A1

ConneXium

Ethernet Gateway

2/2006

Setup

© 2006 Schneider Electric. All Rights Reserved.

5

EN

G

L

IS

H

SETUP

To access the Setup web page links, click Setup on the ETG menu bar.

Ethernet and TCP/IP Settings

NOTE: After making changes to the Ethernet parameters and clicking
Apply, the ETG will reboot.

Action

Result

1. From the Setup page, click Ethernet &

TCP/IP.

Opens the Ethernet & TCP/IP page.

2. Select your frame format and media type.

Contact your network administrator if you
do not know.

Selects the frame format and media type.

3. Enter your IP address, subnet mask, and

default gateway address assigned to your
ETG by your network administrator.

Enters the Ethernet parameters for the ETG.

NOTE: If you enter an IP address that is used
by another device, you will be prompted to
select a new IP address. See “Duplicate IP
Address Detection” on page 6.

4. Click Apply.

Updates the ETG Ethernet and TCP/IP
settings.

* See Table 2 on page 5 for a list of options.

Figure 2:

Ethernet & TCP/IP Page

Table 2:

ETG Ethernet and TCP/IP Settings

Option

Description

Setting

Frame Format

Used to select the format for data sent over
an Ethernet connection.

Ethernet II, 802.3 SNAP

Default: Ethernet II

Media Type

Used to define the physical Ethernet
connection or media type.

10T/100Tx Auto

10BaseT-HD

10BaseT-FD

100BaseTX-HD

100BaseTX-FD

Default: 10T/100Tx Auto

IP Address

Used to enter the static IP address of the
ETG.

0.0.0.0 to 255.255.255.255

Default: 169.254.0.10

Subnet Mask

Used to enter the Ethernet IP subnet mask
address of your network.

0.0.0.0 to 255.255.255.255

Default: 255.255.0.0

Default Gateway

Used to enter the gateway (router) IP
address used for wide area network (WAN)
communications.

0.0.0.0 to 255.255.255.255

Default: 0.0.0.0