Slave Mode Device List Setup

Serial port slave mode allows serial Modbus master devices to access
information from serial slave devices across a TCP/IP network. Figure 6
below illustrates how the devices are connected using the device list
settings in Figure 7.

If you selected Slave mode on the Serial Port page, follow the steps below
to set up the device list:

Figure 6:

Slave Mode Topology

2

5

2

3

4

5

6

7

Ethernet

Connection

ETG in

master mode

IP address:

169.254.0.75

RS485

connection

Serial Slave Devices

RS232 or RS485

connection

Up to 16 remote IP connections
with up to 128 serial slave devices
are possible

ETG in

slave mode

ETG in master

mode

IP address:

169.254.0.28

Serial Slave Devices

RS485

connection

Action

Result

1. From the Setup page, click Device List.

Opens the Device List page.

2. Select the number of viewable devices (1 to

128), then click Apply.

Selects the number of viewable locations that
can be used to define remote Modbus TCP/IP
devices.

3. In the Local ID text box, type the local ID

(address) of the serial slave device.

Enters the address of the device that the local
Modbus master device will use to access the
remote device.

4. In the Remote ID text box, type the remote

ID (address) of the serial slave device.

Enters the serial slave address of the remotely
connected device.

5. Select the Connection.

Selects the Modbus TCP/IP address to
associate with the remote ID.

6. Repeat steps 3 through 5 until all of the

devices are entered.

Enters all of the mapping information for the
ETG to communicate to the remote devices.

7. Click Apply.

Updates the Device List settings.