Serial port, En g l is h – Schneider Electric TSXETG100 User Manual

Page 7

Advertising
background image

63230-319-211A1

ConneXium

Ethernet Gateway

2/2006

Setup

© 2006 Schneider Electric. All Rights Reserved.

7

EN

G

L

IS

H

Serial Port

Action

Result

1. From the Setup page, click Serial Port.

Opens the Serial Port page.

2. Select your mode, physical interface,

transmission mode, baud rate, parity, and
response timeout (see Table 4 on page 7).

Selects the serial port options.

3. If you select Slave mode, enter the IP

addresses for the remotely connected
devices (see Table 4 on page 7).

Enters the IP addresses of the remote devices.

4. Click Apply.

Updates the ETG Serial Port settings.

Figure 3:

Serial Port Page

Table 4:

Serial Port Settings

Option

Description

Setting

Mode

Used to select how the COM port on the
ETG is utilized (master or slave).

NOTE: When the Mode is changed, the
ETG reboots.

Master, Slave

Default: Master

Physical Interface

Used to select how the ETG serial port is
physically wired.

RS485 4-wire, RS485 2-wire,
or RS232

Default: RS485 2-wire

Transmission
Mode

Used to select how data is transmitted over
a serial connection.

Modbus RTU, Modbus ASCII

Default: Modbus RTU

Baud Rate

Used to select the data transmission speed
over a serial connection.

2400, 4800, 9600, 19200,
38400, 56000*, 57600*

Default: 19200

Parity

Used to select if data is checked for
accuracy using a parity bit.

Even, None

Default: Even

Response Timeout Used to select how long the ETG will wait

to receive a response from a serial device.

0.1 to 10 seconds

Default: 3 seconds

Remote Modbus
TCP/IP
Connections
(Slave mode only)

Used to define a list of Modbus TCP/IP
addresses for the ETG to use during slave
mode communications.

* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.

Advertising