Chapter 2 Installation

Series 24-HP Instruction Manual

2-20

IM-24-HP

4-20 mA Output Connections

The standard Innova-Mass Flow Meter has a single 4-20 mA loop. Two
additional loops are available on the optional communication board. The
4-20 mA loop current is controlled by the meter electronics. The electron-
ics must be wired in series with the sense resistor or current meter. The
current control electronics require 12 volts at the input terminals to oper-
ate correctly.

The maximum loop resistance (load) for the current loop output is depen-
dent upon the supply voltage and is given in Figure 2-16. The 4-20 mA
loop is optically isolated from the flow meter electronics.

R

load

is the total resistance in the loop, including the wiring resistance

(R

load

= R

wire

+ R

sense

). To calculate R

max

, the maximum R

load

for the loop,

use the maximum loop current, 20 mA. The voltage drop in the loop due
to resistance is 20 mA times R

load

and this drop is subtracted from the in-

put voltage. Thus:

The maximum resistance R

load

= R

max

= 50 * (V

supply

– 12V).

Figure 2-16. Load Resistance Versus Input Voltage


Figure 2-17. Isolated 4–20 mA Output with External Power Supply