Series 24-HP Instruction Manual
Appendix E MODBUS Commands
IM-24-HP
E-9
The unit responds with an identical message to that transmitted, and the totalizer
is reset. If the “coil” is turned off as in the following message, the response is al-
so identical to the transmitted message, but the totalizer is not affected.
01 05 00 00 00 00 CD CA
01 Device address
05 Function code 5 = write single coil
00 00 Coil address = 0
00 00 Data to “turn off coil” does not reset totalizer
CD CA CRC