6 Inspections

4.0

I

NSPECTIONS

4.1

External Inspections

1. While the UPS system is still on the truck, inspect the equipment and shipping container(s)

for any signs of damage or mishandling. Do not attempt to install the system if damage is

apparent. If any damage is noted, file a damage claim with the shipping agency within 24

hours and contact Liebert Global Services at 1-800-543-2378 to inform them of the damage

claim and the condition of the equipment.

2. Locate the bag containing the keys for the front access door. The bag is attached to the

cabinet.

3. Compare the contents of the shipment with the bill of lading. Report any missing items to the

carrier and to Liebert Global Services immediately.

4. Check the nameplate on the cabinet to verify that the model number corresponds with the one

specified. Record the model number and serial number in the front of this installation

manual. A record of this information is necessary should servicing become required.

4.2

Internal Inspections

1. Verify that all items have been received.
2. If spare parts were ordered, verify arrival.
3. Open doors and remove cabinet panels to check for shipping damage to internal components.
4. Check for loose connections or unsecured components in the cabinet(s).
5. Check for installation of circuit breaker line safety shields. There should be no exposed circuit

breaker terminals when the cabinet doors are opened.

6. Check for any unsafe condition that may be a potential safety hazard.
7. UPS modules are shipped with internally mounted shipping brackets. The shipping brackets

(painted orange) must be removed from the rear (remove rear panels).