Figure 5, Preferred battery cabinet grounding configuration – Liebert 600T User Manual

Page 23

Advertising
background image

Configuring Your Ground and Neutral Connections 17

7.5

Preferred Grounding Configuration, Battery Systems

Figure 5

Preferred Battery Cabinet Grounding Configuration

Large, open-rack battery systems are normally either locally grounded or left ungrounded,

depending on local code requirements.
Battery cabinet systems, on the other hand, should be grounded to the UPS ground bus bar. Fig-

ure 7 above illustrates how a simple one-cabinet system would be grounded. For systems with

multiple cabinets, the same configuration would apply. However, for simplicity the installer can

connect all the battery cabinet grounds together and run a single ground conductor (in the same

conduit as the phase conductors) to the UPS ground.

GROUNDING
ELECTRODE
PER NEC 250-24

TO OUTPUT
DISTRIBUTION