24 Wiring Inspection

Table 1

Power Wiring Terminals - Factory Supplied

UPS Module Rating

kVA

Connection Type

500-750 kVA

Bus bars for connecting hardware (with 3/8” holes on 1.75” centers) are provided
for bypass input, critical load output and DC wiring terminations. DC bus bars for
625-750 kVA modules are designed for top entry and are located adjacent to the
input circuit breaker. Rectifier input wiring is top-entry, directly to lugs on top of
the input circuit breaker. Field-supplied lugs are required.
EXCEPTION: 500 kVA UPS modules with the 6-pulse rectifier and no input
isolation transformer have rectifier input bus bars exactly like those described
above for bypass and critical load termination.

Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this manual)
and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Refer to Appendix B
- Field Supplied Lugs
. Connect wire to the lug using tool and procedure specified by the lug manufacturer.

Table 2

Torque Specifications

Nut and Bolt Combinations

Bolt Shaft Size

Grade 2

Standard

Electrical Connections

with Belleville Washers

Lb-in

N-m

Lb-in

N-m

1/4

53

6.0

46

5.2

5/16

107

12

60

6.8

3/8

192

22

95

11

1/2

428

48

256

29

Circuit Breakers With Compression Lugs (For Power Wiring)

Cable Size or Range

Lb-in

N-m

#6 - #4

100

11

#3 - #1

125

14

1/0 - 2/0

150

17

3/0 - 200 MCM

200

23

250 - 400 MCM

250

28

500 - 700 MCM

300

34

Terminal Block Compression Lugs (For Control Wiring)

AWG Wire Size or Range

Lb-in

N-m

#22 - #14

3.5 to 5.3

0.4 to 0.6

Use the values in this table unless the equipment is labeled with a
different torque value.