Liebert 600T User Manual

Page 7

Advertising
background image

1

I

MPORTANT

S

AFETY

I

NSTRUCTIONS

Save These Instructions.

This manual contains important instructions that should be followed during installation of your

Series 600T UPS and batteries.

!

WARNING
EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS

TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL.

THE UPS MODULE WEIGHT RANGES FROM 4200 POUNDS

(1909 KG) TO 9170 POUNDS (4170 KG), INCLUDING

TRANSFORMER CABINET. THE BATTERY CABINETS WEIGH

BETWEEN 3000 POUNDS (1364 KG) AND 4900 POUNDS (2227 KG).
LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING

EACH CABINET. TEST LIFT AND BALANCE THE CABINETS

BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM

VERTICAL AT ALL TIMES.
SLOTS AT THE BASE OF THE MODULES AND BATTERY

CABINETS ARE INTENDED FOR FORKLIFT USE. BASE SLOTS

WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE

COMPLETELY BENEATH THE UNIT.
FOLLOW ALL BATTERY SAFETY PRECAUTIONS WHEN

INSTALLING, CHARGING, OR SERVICING BATTERIES. IN

ADDITION TO THE HAZARD OF ELECTRIC SHOCK, GAS

PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND

SULFURIC ACID CAN CAUSE SEVERE BURNS.
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT,

ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE

APPROVED FOR USE IN ELECTRICAL FIRE FIGHTING,

SHOULD BE USED.
EXTREME CAUTION IS REQUIRED WHEN PERFORMING

MAINTENANCE.
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS

HIGH DC AS WELL AS AC VOLTAGES.
CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS

PRIOR TO MAKING CONTACT.