Liebert 600T User Manual
Page 70
64 Appendix A - Site Planning Data
Table 5
Site Planning Data, 600 Volt Input
Table 6
Circuit Breaker Ratings
UPS Rating
AC
Output
Voltage
Options
Rectifier AC
Input Current
Inverter or
Bypass Out-
put Current
Required
Battery
Discon-
nect
Maximum
Battery
Current at
End of
Maximum
Heat Dissi-
pation
(BTU/Hr)
Dimensions
Inches
Approx.
Weight
Floor
Loading
(Lb/Sq Ft)
(concen-
kVA
kW
Input
Filter
Input
Xfmr
Nom
Max
Nom
Max
Rating
(Amperes)
Discharge
(Amperes)
Full Load
(WxDxH)
(unpacked)
trated
loading)
500
400
600
NO
NO
484
605
481
601
1,000
1,079
94,900
72x39x79
6,175
317
500
400
600
YES
NO
449
561
481
601
1,000
1,079
99,600
72x39x79
6,375
327
500
400
600
NO
YES
490
612
481
601
1,000
1,079
110,700
96x39x79
8,775
338
500
400
600
YES
YES
454
567
481
601
1,000
1,079
115,500
96x39x79
8,975
345
500
450
600
NO
NO
545
681
481
601
1,200
1,214
106,750
72x39x79
6,195
318
500
450
600
YES
NO
505
631
481
601
1,200
1,214
112,050
72x39x79
6,395
328
500
450
600
NO
YES
551
688
481
601
1,200
1,214
124,550
96x39x79
9,095
350
500
450
600
YES
YES
510
638
481
601
1,200
1,214
129,950
96x39x79
9,295
358
625
500
600
NO
NO
602
753
601
752
1,400
1,349
108,950
108x39x79
7,900
270
625
500
600
YES
NO
559
699
601
752
1,400
1,349
118,650
108x39x79
8,120
278
625
500
600
NO
YES
609
761
601
752
1,400
1,349
128,450
120x39x79
10,580
326
625
500
600
YES
YES
554
705
601
752
1,400
1,349
134,400
120x39x79
10,800
332
750
600
600
NO
NO
723
903
722
902
1,600
1,619
130,700
108x39x79
8,500
291
750
600
600
YES
NO
671
839
722
902
1,600
1,619
142,350
108x39x79
8,720
298
750
600
600
NO
YES
730
913
722
902
1,600
1,619
154,150
120x39x79
11,580
356
750
600
600
YES
YES
677
846
722
902
1,600
1,619
161,250
120x39x79
11,800
363
750
675
600
NO
YES
822
1027
722
902
1,600
1,822
173,400
120x39x79
11,880
366
750
675
600
YES
YES
762
952
722
902
1,600
1,822
181,400
120x39x79
12,100
372
13
1,4,5,7,8,
9,11,12
2,3,5,7,8,
9,11,12
6
6,8,9,
11,12
UPS
Module
Input
Input Breaker Ratings (Amps)
Output and Bypass
Breaker Ratings (Amps)
kVA
Ratings
Voltage
Frame
Trip
Interrupting
(KAIC)
Frame
Trip
Interrupting
(KAIC)
500 (400 kW)
480
1000
800
65
1000
900
65
500 (400 kW)
600
1000
700
42
1000
700
42
500 (450 kW)
480
1000
900
65
1000
900
65
500 (450 kW)
600
1000
700
42
1000
700
42
625 (500 kW)
480
1000
1000
65
1000
1000
65
625 (500 kW)
600
1000
800
42
1000
800
42
750 (600 kW)
480
1200
1100
65
1200
1100
65
750 (600 kW)
600
1000
1000
42
1000
1000
42
750 (675 kW)
480
1200
1200
65
1200
1100
65
750 (675 kW)
600
1200
1000
42
1200
1000
42