Liebert 600T User Manual

Page 70

Advertising
background image

64 Appendix A - Site Planning Data

Table 5

Site Planning Data, 600 Volt Input

Table 6

Circuit Breaker Ratings

UPS Rating

AC

Output

Voltage

Options

Rectifier AC

Input Current

Inverter or

Bypass Out-

put Current

Required

Battery

Discon-

nect

Maximum

Battery

Current at

End of

Maximum

Heat Dissi-

pation

(BTU/Hr)

Dimensions

Inches

Approx.

Weight

Floor

Loading

(Lb/Sq Ft)

(concen-

kVA

kW

Input
Filter

Input

Xfmr

Nom

Max

Nom

Max

Rating

(Amperes)

Discharge

(Amperes)

Full Load

(WxDxH)

(unpacked)

trated

loading)

500

400

600

NO

NO

484

605

481

601

1,000

1,079

94,900

72x39x79

6,175

317

500

400

600

YES

NO

449

561

481

601

1,000

1,079

99,600

72x39x79

6,375

327

500

400

600

NO

YES

490

612

481

601

1,000

1,079

110,700

96x39x79

8,775

338

500

400

600

YES

YES

454

567

481

601

1,000

1,079

115,500

96x39x79

8,975

345

500

450

600

NO

NO

545

681

481

601

1,200

1,214

106,750

72x39x79

6,195

318

500

450

600

YES

NO

505

631

481

601

1,200

1,214

112,050

72x39x79

6,395

328

500

450

600

NO

YES

551

688

481

601

1,200

1,214

124,550

96x39x79

9,095

350

500

450

600

YES

YES

510

638

481

601

1,200

1,214

129,950

96x39x79

9,295

358

625

500

600

NO

NO

602

753

601

752

1,400

1,349

108,950

108x39x79

7,900

270

625

500

600

YES

NO

559

699

601

752

1,400

1,349

118,650

108x39x79

8,120

278

625

500

600

NO

YES

609

761

601

752

1,400

1,349

128,450

120x39x79

10,580

326

625

500

600

YES

YES

554

705

601

752

1,400

1,349

134,400

120x39x79

10,800

332

750

600

600

NO

NO

723

903

722

902

1,600

1,619

130,700

108x39x79

8,500

291

750

600

600

YES

NO

671

839

722

902

1,600

1,619

142,350

108x39x79

8,720

298

750

600

600

NO

YES

730

913

722

902

1,600

1,619

154,150

120x39x79

11,580

356

750

600

600

YES

YES

677

846

722

902

1,600

1,619

161,250

120x39x79

11,800

363

750

675

600

NO

YES

822

1027

722

902

1,600

1,822

173,400

120x39x79

11,880

366

750

675

600

YES

YES

762

952

722

902

1,600

1,822

181,400

120x39x79

12,100

372

13

1,4,5,7,8,

9,11,12

2,3,5,7,8,

9,11,12

6

6,8,9,
11,12

UPS

Module

Input

Input Breaker Ratings (Amps)

Output and Bypass

Breaker Ratings (Amps)

kVA

Ratings

Voltage

Frame

Trip

Interrupting

(KAIC)

Frame

Trip

Interrupting

(KAIC)

500 (400 kW)

480

1000

800

65

1000

900

65

500 (400 kW)

600

1000

700

42

1000

700

42

500 (450 kW)

480

1000

900

65

1000

900

65

500 (450 kW)

600

1000

700

42

1000

700

42

625 (500 kW)

480

1000

1000

65

1000

1000

65

625 (500 kW)

600

1000

800

42

1000

800

42

750 (600 kW)

480

1200

1100

65

1200

1100

65

750 (600 kW)

600

1000

1000

42

1000

1000

42

750 (675 kW)

480

1200

1200

65

1200

1100

65

750 (675 kW)

600

1200

1000

42

1200

1000

42

Advertising