Lathem Dukane 24A715 User Manual

Page 45

Advertising
background image

Please note that the relay contacts used in the CLK2 circuit are rated at 10 amps. The
combined load of the correction circuit and the run circuit should not exceed 8 amps. In
general, 20–35 analog clocks can be operated on a single string. This number depends on
the clock style and the distances involved. To estimate clock loads for Dukane 24SS se-
ries clocks, see the Dukane Analog Clock Installation Guide (document number
402-455).

24A715/24A715M Master Clock Installation Manual

B-3

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

24 OR 120 VAC

10 ASB MAX.

NEUTRAL

CORRECTION CIRCUIT
TO CORRECTION COIL

RUN CIRCUIT TO
ANALOG CLOCK MOTOR

1

1

1 = V250LA4 MOV or equal

NEUTRAL

Figure B-1

Three-Wire Synchronous (59th Minute, Dukane 24SS)