TYPE 04—Standard Electric Time AR-2A Two-Wire, Dual Voltage

Each minute, from 58 seconds to 00 seconds, a low-voltage pulse (24Vdc) is transmitted.
The secondary clocks receive the pulses until the 59th minute. At this time, from 50 sec-
onds to 00 seconds, a higher voltage pulse (48Vdc) is required to advance to the hour.

Manual clock advances and daylight saving advances cause the master clock to transmit
62 pulses (one second ON and one second OFF at 0.5Hz), all at 24Vdc. Normal minute
pulses are inhibited during these pulses.

24A715/24A715M Master Clock Installation Manual

B-7

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

RTN

10 ASB MAX.

24Vdc

AB

PC

2 = 1N4004 diode or equal

48Vdc

2

Figure B-5

Standard Electric Time AR-2A Two-Wired, Dual Voltage