TYPE 19—Stromberg Synchronous Wired (56th Minute)

For a list of Type 19 clocks, see the chart on the first page of this appendix.

This clock is normally operated by 120Vac/24Vac. Relay K5 is normally operated to sup-
ply motor power. Relay K6 activates each hour from HH:56:10 to HH:56:18, causing an
eight-second signal to be transmitted on the correction line for hourly correction. Relay
K6 activates every 12 hours, from 11:56:36 to 11:56:50, causing an additional 14-second
signal to be transmitted on the correction line for 12-hour correction. During power inter-
ruptions and automatic clock resetting, relay K5 is deactivated.

Note:
Lathem SS Modified wall clocks operate according to the above signal operation if
modified to reference the minute and second hands to HH:57:16 (versus HH:59:00)
and the hour hand to 12:00 (versus 6:00).

24A715/24A715M Master Clock Installation Manual

B-25

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

120Vac

10 ASB MAX.

CORRECTION COIL

RUN MOTOR

RETURN

1 = V250LA4 MOV or equal

1

1

1

AC RTN

Figure B-22

Stromberg Synchronous Wired (56th Minute)