B-31, B-28 – Lathem Dukane 24A715 User Manual

Page 73

Advertising
background image

TYPE 27—Simplex 2310 Dual Motor

Type 27 secondary clocks have the same hourly corrections as type 09, with the addition
of 12-hour corrections as for type 03.

Power is normally applied to the 1 RPM run motor. Each hour, from HH:58:05 through
HH:58:59, power is removed from the run motor and applied to the fast advance motor.
During manual clock corrections, power is applied to both motors for 4 minutes and 15
seconds.

During normal operation, 120Vac is applied to the run motor. A 15-minute correction
signal on the correction motor line causes a 12-hour correction from 5:12:00 to 5:28:00.
This occurs twice daily (AM and PM). Run motor power is connected during the 12-hour
correction. A 29-second signal is applied to the correction motor line from HH:59:30 to
HH:59:59 to cause hourly corrections. During hourly corrections, power is disconnected
from the run motor line.

Types 28, 29, and 30

For wiring information on Type 28 (Stromberg 12-hour), Type 29 (Type 01 Special), and
Type 30 (Type 14 Special) clocks, contact Lathem Time Corporation.

24A715/24A715M Master Clock Installation Manual

B-31

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

AC RTN

10 ASB MAX.

120Vac

FAST ADVANCE MOTOR

1 RPM RUN MOTOR

RETURN

1 = V250LA4 MOV or equal

1

1

CODE 09 = 59TH MIN.
CODE 10 = 45TH MIN.

Figure B-28

Simplex 2310 Dual Motor