TYPE 03—Standard Electric Synchronous

During normal operation, 120Vac is applied to the run motor. A 15-minute correction
signal on the correction motor line causes a 12-hour correction from 5:12:00 to 5:28:00.
This occurs twice daily (AM and PM). Run motor power is connected during the 12-hour
correction. A 29-second signal is applied to the correction motor line from HH:59:30 to
HH:59:59 to cause hourly corrections. During hourly corrections, power is disconnected
from the run motor line.

B-6

24A715/24A715M Master Clock Installation Manual

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

AC RTN

10 ASB MAX.

120Vac

CORRECTION MOTOR

RUN MOTOR

1 = V250LA4 MOV or equal

1

1

RETURN

Figure B-4

Standard Electric Synchronous