Trouble diagnosis – LG SXS GR-P257/L257 User Manual

Page 78

Advertising
background image

TROUBLE DIAGNOSIS

- 76 -

Items

Precautions

4.Vacuum degassing.

Pipe Connection

Connect a red hose to the high pressure side and a blue hose to the

low pressure side.

Vacuum Sequence

Open

ቢ, ባ valves and evacuate for 40 minutes. Close valve ቢ.

5.Refrigerant charging.

Charging sequence

1) Check the amount of refrigerant supplied to each model after completing vacuum

degassing.

2) Evacuate bombe with a vacuum pump.

3) Measure the amount of refrigerant charged.

- Measure the weight of an evacuated bombe with an electronic scale.

- Charge refrigerant into a bombe and measure the weight. Calculate the weight of

refrigerant charged into the bombe by subtracting the weight of an evacuated bombe.

KEYPOINTING
- If power is applied

during vacuum
degassing, vacuum
degassing shall be
more effective.

- Operate compressor

while charging
refrigerant. (It is
easier and more
certain to do like
this.)

KEYPOINTING
- Be sure to charge

the refrigerant at
around 25°C.

- Be sure to keep -5g

in the winer and
+5g in summer

the amount of refrigerant charged= a weight after charging -
a weight before charging (a weight of an evacuated cylinder)

Calculation of amount of refrigerant charged

2

1

3

Compressor

Low

pressure

Condenser

High

pressure

Drier

Evaporator

Red

Yellow

Blue

Vaccum

Pump

Suction pipe

R134a

Indicate the weight of
an evacuated bombe