Gas connections, Table - 3d – Lochinvar COPPER-FINN2 502 User Manual

Page 33

Advertising
background image

33

3

Gas connections

(continued)

SUPPLY

INLET

PRESSURE

TAP

INLET

GAS

VALVE

CONTROL

KNOB

OUTLET

Installation & Operation Manual

Figure 3-3_Measuring Gas Supply Pressure at
Combination Gas Valve

13. Remove the manometer and related fitting from the “inlet”

side of the gas valve, replace 1/8" hex plug in gas valve and
tighten.

14. Turn on gas supply at the manual valve, turn on L.P. gas at

the tank if required.

15. Turn the power switch to the “ON” position.

16. Turn the gas valve knob to the “ON” position.

17. Set the electronic temperature control or thermostat to call

for heat.

Combination gas valve/regulators equipped with integral vent
limiters are not required to have vent or relief lines piped to
the outdoors. The termination of the vent limited opening on
the combination gas valve/regulator complies with the safety
code requirements of CSD-1, CF-190(a) as shipped from the
appliance manufacturer without the installation of additional
vent lines.

Checking gas supply pressure

Use the following procedure to check gas supply pressure.

1. Turn the main power switch to the “OFF” position.

2. Turn gas valve knobs to the “OFF” position.

3. Shut off gas supply at the field-installed manual gas cock in

the gas piping to the unit. If fuel supply is L.P. gas, shut off
gas supply at the tank.

4. Remove the 1/8" hex plug, located on the “inlet” side of the

gas valve. You may also use a tapping on the field-installed
main manual gas cock or gas piping. Install a fitting in the
inlet pressure tapping suitable to connect to a manometer
or magnehelic gauge. Range of scale should be 14" w.c. or
greater to check inlet pressure.

5. Turn on gas supply at the manual gas cock, turn on L.P. gas

at the tank if required.

6. Turn the power switch to the “ON” position.

7. Turn the gas valve knobs to the “ON” position. Set the

electronic temperature control or thermostat to call for
heat.

8. Observe the gas supply pressure as all burners are firing.

Ensure that inlet pressure is within the specified range.
See Connecting To Gas Supply, page 31 for minimum and
maximum gas supply pressures.

9. If gas pressure is out of range, contact gas utility, gas

supplier, qualified installer or service agency to determine
necessary steps to provide proper gas pressure to the
control.

10. If gas supply pressure is within normal range, turn the

power switch to the “OFF” position.

11. Turn gas valve knobs to the “OFF” position.
12. Shut off gas supply at the manual gas cock in the gas piping

to the unit. If fuel supply is L.P. gas, shut off gas supply at
the tank.

TABLE - 3D

GAS PIPING SIZE CHART

Nominal

Iron Pipe

Size

Inches

Length of Pipe in Straight Feet

Maximum

Capacity of Pipe
in Thousands of

Btu/hr per hour

for gas pressures

of 14 Inches

Water Column

(0.5 PSIG) or less

and a pressure

drop of 0.5 Inch

Water Column

(Based on NAT

GAS, 1025 Btu/hr

per Cubic Foot

of Gas and 0.60

Specific Gravity)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1

697

477

384

328

292

267

246

256

210

200

179

164

149

138

1 1/4

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

1 1/2

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

2

4,100

2,820

2,260

1,950

1,720

1,560 1,440 1,330

1,250

1,180

1,100

974

871

820

2 1/2

6,460

4,460

3,610

3,100

2,720

2,460 2,310 2,100

2,000

1,900

1,700 1,540 1,400

1,300

3

11,200

7,900

6,400

5,400

4,870

4,410 4,000 3,800

3,540

3,300

3,000 2,720 2,500

2,340

4

23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690

7,380

6,870

6,150 5,640 5,130

4,720

ƽ WARNING

After completing any testing on the gas
system, leak test all gas connections. Apply
a soap/water solution to all gas connections
while main burners are operating. Bubbles
forming indicate a leak. Repair all leaks at
once. Do not operate this unit with a leak in
the gas train, valves or related piping.

Check burner performance by cycling the system while you
observe burner response. Burners should ignite promptly.
Flame pattern should be stable, see Burner Flames in the
Copper-fin

2

Service Manual. Turn system off and allow burners

to cool, then cycle burners again to ensure proper ignition and
flame characteristics.

Advertising
This manual is related to the following products: