Water connections, Installation & operation manual – Lochinvar COPPER-FINN2 502 User Manual

Page 38

Advertising
background image

38

4

Water connections

Figure 4-7_Multi-stack frame - Cascaded heaters beyond 15 feet of pool piping

Installation & Operation Manual

AUTOMATIC
BYPASS VALVE

RECOMMENDED
ISOLATION
VALVE

PRIMARY
LOCATION
POOL
SUPPLY
SENSOR

POOL
RETURN
SENSOR
LOCATION

COPPER
OR PVC
(SEE TABLE)

110

°

LIMIT

3'

MIN

FROM
POOL

TO

POOL

4" PVC

4" PVC

FLOWMETER

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

MODELS 502-752 MODELS 992-2072

1

2"

2-1/2"

2

3"

4"

3

3-1/2"

4"

4

4"

5"

5

5"

6"

6

5"

6"

NUMBER

OF UNITS

COMMON PIPE SIZE (MIN)

TABLE 4A

PIPE SIZING CHART

MEMBER

LEADER

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for
all equipment and detailing required by local codes.

NOTICE

Advertising