Water connections, Installation & operation manual, Figure 4-3_ heater within 15 feet of pool piping – Lochinvar COPPER-FINN2 502 User Manual

Page 36: Figure 4-4_ heater beyond 15 feet of pool piping

Advertising
background image

36

4

Water connections

Figure 4-3_Heater Within 15 feet of Pool Piping

Installation & Operation Manual

Figure 4-4_Heater Beyond 15 feet of Pool Piping

AUTOMATIC

BYPASS VALVE

PVC MIN
(SEE TABLE)

RECOMMENDED
ISOLATION VALVE

REQUIRED POOL
RETURN SENSOR
LOCATION

POOL RETURN SENSOR *
SECONDARY LOCATION

20'

MAX

POOL RETURN SENSOR
PRIMARY LOCATION

COPPER OR PVC
(SEE TABLE)

110

°

LIMIT

3'

MIN

FROM

POOL

TO

POOL

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

* NOTE: IF THE RETURN SYSTEM SENSOR IS
LOCATED IN THE SECONDARY
LOCATION SHOWN ON THE PIPING
DIAGRAM, THE UNIT PUMP MUST
RUN CONTINUOUSLY TO ENSURE
THE WATER FLOW PAST THE
SENSOR IS MAINTAINED.

AUTOMATIC

BYPASS VALVE

PVC MIN
(SEE TABLE)

RECOMMENDED
ISOLATION VALVE

REQUIRED POOL
RETURN SENSOR
LOCATION

POOL RETURN SENSOR *
SECONDARY LOCATION

20'

MAX

POOL RETURN SENSOR
PRIMARY LOCATION

COPPER OR PVC
(SEE TABLE)

110

LIMIT

3'

MIN

FROM

POOL

TO

POOL

VALVE

12"

MAX

OR
4X PIPE
DIAMETERS

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

* NOTE: IF THE RETURN SYSTEM SENSOR IS
LOCATED IN THE SECONDARY
LOCATION SHOWN ON THE PIPING
DIAGRAM, THE UNIT PUMP MUST
RUN CONTINUOUSLY TO ENSURE
THE WATER FLOW PAST THE
SENSOR IS MAINTAINED.

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for
all equipment and detailing required by local codes.