Operating information – Lochinvar COPPER-FINN2 502 User Manual

Page 56

Advertising
background image

56

Installation & Operation Manual

7

Operating information

Status Display Screens

(cont’d)

By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display
screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they
can display:

Screen #

Display shows:

Description

Screen #3

Line 2

SYSRTN: ***F (***)

The system return sensor acts as the control sensor. The control
will display the system return temperature as well as the set point in
parenthesis.

SYSRTN: OPEN

The control does not detect the system return sensor.

SYSRTN: SHORTED

The system return sensor wires or the sensor itself has become shorted.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #4.

N/A

Press the Next  arrow key on the SMART SYSTEM display to access Screen #5.

Screen #5

Line 2

STG DEMAND: ****

The control displays the number of stages firing, based upon demand.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #6.

Screen #6

Line 1

FAN SPEED: ***

The control will display either OFF, LOW, or HIGH depending upon
fan speed requirements of number of stages firing.

Screen #6

Line 2

0 – 10V RATE: **.*V

The control will display 0 to 10 volts based upon fan speed and unit
capacity.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #7.

Screen #7

Line 1

PH CFH: ***

The control will display either ON or OFF based upon a demand (call
for heat) for heat.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #8.

Screen #8

Line 1

SYS PUMP: ***

The control will display either ON or OFF based upon system pump
requirements upon demand.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #9.

Screen #9

Line 1

UNIT PUMP: ***

The control will display either ON or OFF based upon unit pump
requirements upon demand.

UNIT PUMP: DELAY

The control will display delay in unit pump operation after the heat
requirements have been satisfied.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #10.

Screen #10

Line 1

FLM SIG – A: **.* µA

The control displays the igniter flame signal of igniter A in microamps.

Screen #10

Line 2

FLM SIG – B: **.* µA

The control displays the igniter flame signal of igniter B in microamps.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #11.

Screen #11

Line 1

IGN * AMPS: *.* A

The control displays the current of either igniter A or B.

Screen #11

Line 2

MIX VAL POS: ** %

The control displays the mixing valve percentage open to the system.