Electrical connections

Installation & Operation Manual

3-way automatic bypass valve wiring

If the piping loop was disassembled for shipping or needs to be
fitted with an outdoor enclosure, connection or disconnection
of the 3-way automatic bypass valve will be required. Wiring
connections should be made to the appropriately numbered
terminals on the 3-way automatic bypass valve as follows:

Note: Orientation of the valve connections may vary from what
is shown. Care should be taken to ensure wires are connected to
the appropriate terminals, see FIG. 4-8 on page 39 of this manual.

NOTICE

DO NOT block access to the electrical cover
plate when installing electrical conduit.

ƽ WARNING

Power must be removed and the clutch
button must be depressed before attempting
to manually operate the valve, or damage to
the 3-way valve may occur.

TABLE-5B

Remote Wire Connection

Wire

Gauge

Maximum

Allowable Length

12 GA

100 ft.

14 GA

75 ft.

16 GA

50 ft.

18 GA

30 ft.

Figure 5-1_Control Panel Component Location

TRANSFORMER

RELAY

MAIN CONTROL
BOARD

WIRE HARNESS
CONNECTIONS

BREAKER
LOCATION

OPTIONAL
AUXILIARY
HIGH LIMIT
LOCATION

LWCO/SWITCH
LOCATION

ON/OFF
SWITCH

ELECTRICAL SHOCK HAZARD – For your
safety, turn off electrical power supply before
making any electrical connections to avoid
possible electric shock hazard. Failure to do
so can cause severe personal injury or death.

ƽ WARNING

General information

A 120 VAC, 15 Amp, 1 ph, 60 Hz circuit is required for
operation of the appliance controls.

The appliance, when installed, must be electrically grounded
in accordance with the requirements of the authority having
jurisdiction or in the absence of such requirements, with the
latest edition of the National Electrical Code ANSI/NFPA No.
70. When the unit is installed in Canada, it must conform to
the CAE C22.1, Canadian Electrical Code, Part I and/or local
Electrical Codes. Multiple units connected in a Cascade must
be grounded to the same ground connection.

1. All wiring between the appliance and field installed

devices shall be made with type T wire [63°F (35°C)

rise].
2. All line voltage wire exterior to the appliance must be

enclosed in approved conduit or approved metal clad

cable.
3. The circulating pump must run continuously when

the appliance is being fired.

4. To avoid serious damage, DO NOT energize the

appliance until the system is full of water. Ensure that

all air is removed from the heat exchanger and piping

before beginning initial operation. Serious damage

may result if the appliance is operated without proper

flow.
5. Provide the appliance with proper overload protection.

TABLE-5A

3-Way Automatic Bypass Valve Wiring

Wire

Color

FIELD

FACTORY

3-Way Valve

Low Voltage

Board

1

Blue

Terminal #1

Terminal #19

2

Orange

Terminal #2

Terminal #7

3

Black

Terminal #3

Terminal #6

4

Red

Terminal #4

Terminal #5