Water connections, Installation & operation manual – Lochinvar COPPER-FINN2 502 User Manual

Page 37

Advertising
background image

37

4

Water connections

(continued)

Installation & Operation Manual

Figure 4-5_Cascaded heaters Within 15 feet of Perpendicular Pool Piping

Figure 4-6_Cascaded Heaters Beyond 15 feet of Pool Piping

AUTOMATIC

BYPASS VALVE

RECOMMENDED
ISOLATION
VALVE

* POOL
RETURN
SENSOR
SECONDARY
LOCATION

POOL RETURN SENSOR
PRIMARY LOCATION

110

°

LIMIT

3'

MIN

FROM

POOL

TO

POOL

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

PVC MIN
(SEE TABLE)

VALVE

REQUIRED
POOL
RETURN
SENSOR
LOCATION

COPPER

OR CPVC

(SEE TABLE)

COPPER
OR CPVC
(SEE TABLE)

* NOTE: IF THE RETURN SYSTEM SENSOR IS
LOCATED IN THE SECONDARY
LOCATION SHOWN ON THE PIPING
DIAGRAM, THE UNIT PUMP MUST
RUN CONTINUOUSLY TO ENSURE
THE WATER FLOW PAST THE
SENSOR IS MAINTAINED.

* POOL

RETURN

SENSOR

SECONDARY

LOCATION

RECOMMENDED
ISOLATION
VALVE

REQUIRED

POOL

RETURN

SENSOR

LOCATION

AUTOMATIC
BYPASS
VALVE

POOL
RETURN
SENSOR
PRIMARY
LOCATION

COPPER

OR PVC

(SEE

TABLE)

110

°

LIMIT

3'

MIN

FROM

POOL

TO

POOL

MODEL NO

BYPASS PIPE SIZE

CP (N,L) 502-752

2" MIN

CP (N,L) 992-2072

2-1/2" MIN

3" PVC

4" PVC

FLOWMETER

* NOTE: IF THE RETURN SYSTEM SENSOR IS
LOCATED IN THE SECONDARY
LOCATION SHOWN ON THE PIPING
DIAGRAM, THE UNIT PUMP MUST
RUN CONTINUOUSLY TO ENSURE
THE WATER FLOW PAST THE
SENSOR IS MAINTAINED.

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for
all equipment and detailing required by local codes.