Maintenance, Inspect and clean the heat exchanger, Review with owner – Lochinvar COPPER-FINN2 502 User Manual

Page 61: Oiled bearing circulators

Advertising
background image

Installation & Operation Manual

8

Maintenance

(continued)

61

Inspect and clean the heat exchanger

1. While burners are removed, check the heat exchanger

surface for sooting. If present, heat exchanger must be

cleaned and problem corrected. Proceed as follows.

2. Remove gas manifold(s)/orifice assemblies as described

in steps 1 through 5 in Burner Removal and Cleaning,

page

60.

3. Disconnect wiring from the hot surface igniter and

remove igniter from the door panel to prevent damage to

the

igniter.

4. Remove inner jacket panel mounting screws and slide

door assembly out toward front of the unit. Use

caution to prevent damage to the refractory.

5.

Check “V” baffles and frame runners along front

and back edges of heat exchanger. Remove and clean if

necessary.

6. Remove soot from heat exchanger with a stiff bristle

brush. Use a vacuum to remove loose soot from

surfaces and inner chamber.

7. If necessary, the heat exchanger can be removed. Once the

heat exchanger is removed from the unit, a garden hose

can be used to wash the tubes to ensure that all soot is removed

from the heat exchanger surfaces. Note: Do not wet the unit’s

refractory.

8. Ensure that all burner ports are cleaned to remove any

soot. See Burner Removal and Cleaning, page 60.

9. Carefully reinstall the heat exchanger, “V” baffles, and

frame runners if removed from the unit. Note: Make

sure frame runners seal securely where they contact the

front and rear compartment refractory.

10. Carefully reinstall inner jacket panels, burners,

manifolds, wires and hoses. Use new gasket material to

ensure a proper air seal.

11. Reassemble all gas and water piping. Test for gas leaks.

Upon completion of any testing on the gas
system, leak test all gas connections with a
soap and water solution while main burners
are operating. Do not spray soap and water
solution on the SMART SYSTEM control
module housing. The use of an excessive
amount of soap and water solution can
damage the control. Immediately repair
any leak found in the gas train or related
components. Do not operate an appliance
with a leak in the gas train, valves, or related
piping.

NOTICE

HEAT

EXCHANGER

Figure 8-2_Location of the Heat Exchanger Inside Jacket

Review with owner

1. Review

the

Copper-fin

2

Installation and Operation Manual

with the owner.

2. Emphasize the need to perform the maintenance schedule

specified in this manual.

3. Remind the owner of the need to call a licensed contractor

should the appliance or system exhibit any unusual behavior.

4. Remind the owner to follow the proper shutdown procedure

and to schedule an annual start-up at the beginning of the
next heating season.

Oiled bearing circulators

Inspect the pump every six (6) months and oil as necessary. Use
SAE 30 non-detergent oil or lubricant specified by the pump
manufacturer.

12. Reassemble outer jacket panels.

13. Cycle unit and check for proper operation.