Installation, For qualified installers only) – Lopi Yankee PS User Manual

Page 14

Advertising
background image

1 4

Installation

(For Qualified Installers Only)

© Travis Industries

4080728

1 0 0 - 0 1 1 5 6

Installation Example: Direct "Through-the-wall" Installation

3” Minimum

9” Minimum

Floor Protection

6” Minimum

House Shield (used to protect exterior wall from soot
discoloration) is HIGHLY RECOMMENDED

12” Minimum

Horizontal Rain Cap

Wall Thimble (note
clearance between
vent and
combustibles)

Outside Air

Type "L"

Vent

12”

Minimum

3” Minimum

16-1/2”

9-1/4”

Floor Protection

Seal each vent

section (including

adapters, elbows,

etc...) by injecting a

liberal amount of

500° F. RTV

silicone into the gap

between sections.

500

° F. RTV

Silicone