Installation

(For Qualified Installers Only)

1 5

© Travis Industries

4080728

1 0 0 - 0 1 1 5 6

Installation Example: Interior Vertical Installation

Type "L" Vent

6” Minimum

Vent

Clearance*

Floor Protection

2”

Minimum

9” Minimum

“Tee”

Outside

Air

(optional)

Floor Protection

24” Minimum

Insulation
must maintain
clearance.

Outside air may be drawn from
a ventilated crawl space.

2” Min.

Vent

Clearance*

Ceiling Support / Fire Stop Spacer

Roof Flashing

Storm Collar

Vertical Cap

Vent must
maintain
clearance to
combustibles.

“L” Vent

Seal each vent

section (including

adapters, elbows,

etc...) by injecting a

liberal amount of

500° F. RTV

silicone into the gap

between sections.

500

° F. RTV

Silicone

*

Install vent at clearance specified by the vent manufacturer.