1 examples on plc data entries via html page – Panasonic Web-Server FP User Manual

Page 100

Advertising
background image

FP Web-Server V2.11

7.1 Details on the FP Web-Server's Web Page Functions

89

The individual HTML commands can be entered (exactly as described above) into the HTML
code of the page and then adjusted respectively. Some HTML editors provide additional help
and automatic generation for creating submit fields. The commands have the following
significance:

ACTION="

/plcpost

"

Enter precisely like this. CGI function of the FP
Web-Server.

METHOD="

POST

"

Enter precisely like this. Method of the CGI call.

TARGET="

SUBWIN

"

Enter precisely like this. Display the result in a separate
window.

ONSUBMIT="

opensubwin(200,100)

"

Enter precisely like this. Java Script call and window
size.

Enter DT204

Variable text will be displayed as seen.

NAME="

DT204_5_u

"

Specification of the memory address in the PLC and
interpretation of the input format.

SIZE="

6

"

Width of the input window in number of characters.

VALUE="

{DT204_5_u}

"

Initial value of the input field. Pre-allocation of the Edit
field.

Only for the definition of buttons in case A):

TYPE="

submit

"

Enter precisely like this. Function of the [SUBMIT]
buttons.

NAME="

Button

"

Enter precisely like this. Name of the [SUBMIT] button.

VALUE="

set

"

Variable labeling of the [SUBMIT] buttons.

7.1.12.1 Examples on PLC Data Entries via HTML Page

a) Decimal

numbers

Entry format

User entry

Data in PLC register

DT201_16_u

12

DT201= 12 (0C hex)

DT201_16_d -32768

DT201=

-32768

(8000hex)

DT202_16_ld 1234567

DDT202=1234567

(12D687hex)

DT202_16_f

123.4

DDT202=123.4 (42F6CCCD hex)

DT202_16_f

1.2e4

DDT202=12000 (463B8000 hex)

b) Strings

Entry format

User entry

Data in PLC register

DT602_16_S 1234

DT602-DT603="1234"

DT602_16_S

123

DT602-DT603="123?" (? is unchanged)

DT600_16_s

1234

DT601=4 DT602-DT603="1234" (DT600 > 3)

DT602_16_c

ABC

DT602="A?" (? is unchanged)

c) Hex

entries:

In the latest version also the format type characters 'x' and 'X' are allowed for
hexadecimal PLC data entries. Hex data entries are possible for 16-bit
(name="DT200_6_X") and 32-bit (name="DT300_16_lx") PLC data registers:

Entry format

User entry

Data in PLC register

DT201_16_X

7b

DT201= 123 (007B hex)

Advertising