Set modbus-slave line, Set modbus-master line – Perle Systems 5500208-43 User Manual

Page 50

Advertising
background image

51

Line Service Commands

Set Modbus-Slave Line

Description Sets the Modbus slave parameters for the line.
User Level Admin
Syntax

Options

crlf

protocol

uid-range

Set Modbus-Master Line

<ip_address>

Specify the IP address of the remote host that is receiving the vmodem connection.

<host>

Select the hostname (from the host table) of the remote host that is receiving the

vmodem connection.

<port>

Specify the TCP port that the remote host is listening on for the vmodem connection.

delete
Deletes the specified entry from the phone number table.

set modbus-slave line .|<number>|* [crlf on|off]

[protocol rtu|ascii] [uid-range <uid_range>]

When

Modbus/ASCII

is selected, adds a CR/LF to the end of the transmission; most

Modbus devices require this option. The default is

On

.

Specify the protocol that is used between the Modbus Master(s) and Modbus Slave(s),

either RTU or ASCII.

You can specify a range of UIDs (1-247), in addition to individual UIDs. The format is

comma delimited; for example, 2-35, 50, 100-103.

Description Sets the Modbus master parameters for the line.
User Level Admin
Syntax

set modbus-master line .|<number>|* [crlf on|off]

[protocol rtu|ascii]
[[entry <number> [port <port>] [protocol udp|tcp]
[range-mode gateway|host] [slave-ip <IP_address>]
[uid-range <start_uid> <end_uid>]]

Options

crlf

When

Modbus/ASCII

is selected, adds a CR/LF to the end of the transmission; most

Modbus devices require this option. The default is

On

.

protocol

Specify the protocol that is used between the Modbus Master(s) and Modbus Slave(s),

either RTU or ASCII.

entry

You can specify up to 16 Modbus Slave Remote IP Mapping entries (the UIDs must not
overlap).