Set iochannel analog (temperature) – Perle Systems 5500208-43 User Manual

Page 82

Advertising
background image

Set IOChannel

83

IOLAN DS1/TS2 CLI Reference Guide, Version 4.3

Set IOChannel Analog (Temperature)

Description Sets the Analog input channel settings for Temperature models.
User Level Admin
Syntax

set iochannel <analog_channel> type rtd|thermocouple

range <range_specifier>

set iochannel <analog_channel> alarm

[level 1|2|3|4|5 [mode on|off] [trigger-type disabled|low|high]
[trigger-level <decimal_value>] [clear-mode auto|manual]
[clear-level <decimal_value>] [snmp on|off] [syslog on|off]]

Options

analog_channel

Specify the Analog channel number, for example, a2 or a4 (this also applies to

Temperature models).

type

Specify the type of sensor you are using to measure temperature, either RTD or
thermocouple. The default is RTD.

range

Specify the temperature range that you want to measure. For RTD, the range is:

z

1 (Pt100 a=385 -50 to 150C) This is the default.

z

2 (Pt100 a=385 0 to 100C)

z

3 (Pt100 a=385 0 to 200C)

z

4 (Pt100 a=385 0 to 400C)

z

5 (Pt100 a=385 -200 to 200C)

z

6 (Pt100 a=392 -50 to 150C)

z

7 (Pt100 a=392 0 to 100C)

z

8 (Pt100 a=392 0 to 200C)

z

9 (Pt100 a=392 0 to 400C)

z

10 (Pt100 a=392 -200 to 200C)

z

11 (Pt1000 a=385 -40 to 160C)

z

12 (NiFe604 a=518 -80 to 100C)

z

13 (NiFe604 a=518 0 to 100C)

For thermocouple, the range is:

z

b (B 500 to 1800C)

z

e (E 0 to 1000C)

z

j (J 0 to 760C) This is the default.

z

k (K 0 to 1370C)

z

r (R 500 to 1750C)

z

s (S 500 to 1750C)

z

t (T -100 to 400C).

alarm

Configures alarm settings when the Analog input trigger is activated.