Set IOChannel

Set IOChannel Digital Output (Serial Pins)

Description Sets the Digital output for serial pins RTS and DTR. This option is only available when

the

Line Service

is set to

Signal I/O

.

User Level Admin
Syntax

Options

description

failsafe-action

mode

Set IOChannel Relay

set iochannel rts|dtr [description <string>]

[failsafe-action none|activate-outut|deactivate-output]
[mode enabled|disabled]

Provide a description of the channel, making it easier to identify. The channel

description can be up to 20 characters.

When there has been no I/O activity within the specified time (set in the Global

Settings) and the

Failsafe Timer

is triggered, you can set the

Failsafe Action

to:

z

None—The state of the Digital/Relay output remains the same, no change.

z

Activate Output—Activates the output.

z

Deactivate Output—Deactivates the output.

Enables the channel, allowing the settings to become active.

Description Sets the Relay output channel settings.
User Level Admin
Syntax

set iochannel <relay_number> output

[pulse continuous|counted <pulse_count>]
[active-to-inactive-delay <delay>]
[inactive-to-active-delay <delay>]

set iochannel <relay_number>

[active-signal-width <width>] [inactive-signal-width <width>]
[failsafe-action none|activate|deactivate]

Options

relay_number

Specify the Relay channel number, for example, r2.

output

Specify how the channel Digital output will be handled:

z

Manual—You must manually activate and deactivate the output.

z

Pulse—When the output is activated, this configuration will cause the output to

pulse (go active and inactive) at a configured rate.

z

Inactive-to-Active Delay—The channel output will remain inactive for the

specified time interval after it is manually started.

z

Active-to-Inactive Delay—The channel output will go inactive after the specified
time interval after it is manually started.

The default is

Manual

.

pulse

When the

Output

is

Pulse

, you can have it pulse in a

Continuous

manner or specify a

pulse

Count

(each count consists of an active/inactive sequence). The default is

Continuous

.

Advertising