External Bypass Switch Installation

36

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

QFE: 50 Hz 120 Vac Input and Output OR
FE: 60 Hz 120 Vac Input and Output OR
FE 1.15–3.1 kVA only: 60 Hz 220 Vac Input and Output (with single-voltage output)
For 220 Vac, use only a BBM switch.

Figure 8. FE or QFE 500 VA–3.1 kVA UPS with External Bypass Switch

Table 11. Minimum Recommended Circuit Breakers for 60 Hz 120 Vac

Charger

500 VA, 700 VA, and 850 VA

1.15 kVA

1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

Standard

15

15

15

20

25

35

15A

20

20

40

45

50

Table 12. Input Current for 50 Hz 120 Vac - Size Overcurrent Protection According to Local Code

Voltage and Charger

500 VA

700 VA

850 VA

1.15 kVA

1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

120V, Standard Charger

4.4A

5.8A

7.0A

8.4A

11A

15A

16A

24A

120V, 15A Charger

8.9A

11A

12A

13A

14A

27A

28A

35A

Table 13. Input Current for 60 Hz 220 Vac - Size Overcurrent Protection According to Local Code

60 Hz Voltage

1.15 kVA

1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

220V, Standard Charger

4.6A

5.8A

7.8A

9.4A

12A

220V, 15A Charger

7A

8A

15A

17A

21A