Battery Cabinet Installation

55

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

Table 27. Nominal DC Battery Voltage

Models

Nominal Battery

Voltage

QFE 500 VA, 700 VA, 850 VA, 1.15 kVA, and 1.4 kVA

12 Vdc

FE 500 VA, 700 VA, and 850 VA

24 Vdc

QFE 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and 7 kVA
FE 1.15 kVA, 1.4 kVA, 1.8 kVA, 2.1 kVA, 3.1 kVA, 4.3 kVA, 5.3 kVA, and
7 kVA

48 Vdc

FE and QFE 10 kVA, 12.5 kVA, and 18 kVA

120 Vdc

The battery cable or wire used is #1 AWG (42.11 mm

2

) for all

applications with the following exceptions:
: 18 kVA models use #1/0 (53.49 mm

2

) battery cables.

: If the batteries must be some distance from the UPS, you may need to

install larger battery cables between the battery cabinets and the UPS.
Using long cable runs and larger diameter cables may require
modifications inside the UPS; call your service representative if you
did not order the longer, larger-diameter cable with the UPS.

The UPS must have a DC disconnect switch or a removable plug so you
can disconnect external batteries from the UPS.
: FE/QFE 500 VA–3.1 kVA models have a removable plug at the UPS;

the battery cabinet may also have a DC switch.

: Most FE/QFE 4.3–18 kVA models have a DC switch at the battery

cabinet. However, some may have a removable plug at the cabinet or
between the UPS and the batteries, and others may have an external
DC switch. FE/QFE 4.3–18 kVA models also have a DC switch
behind the front cover panel.