Powerware Ferrups FE/QFE 500VA User Manual
Page 45
Advertising
External Bypass Switch Installation
39
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
:
Rev A www.powerware.com
50 Hz 220, 230, or 240 Vac Input and Output
Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch
Table 16. Input Current - Size Overcurrent Protection According To Local Code
Voltage
Charger
500 VA
700 VA
850 VA
1.15 kVA
1.4 kVA
1.8 kVA
2.1 kVA
3.1 kVA
220 Vac
Standard
2.6A
3.9A
4.4A
4.9A
5.7A
7.9A
8.2A
13A
15A
4.7A
6.0A
6.5A
7.0A
7.8A
14A
15A
19A
230 Vac
Standard
2.5A
3.8A
4.2A
4.6A
5.4A
7.5A
7.8A
12A
15A
4.6A
5.9A
6.3A
6.7A
7.5A
14A
14A
18A
240 Vac
Standard
2.4A
3.5A
4.0A
4.4A
5.2A
7.2A
7.4A
12A
15A
4.6A
5.7A
6.2A
6.6A
7.4A
14A
14A
19A
Advertising