Powerware Ferrups FE/QFE 500VA User Manual

Page 45

Advertising
background image

External Bypass Switch Installation

39

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

50 Hz 220, 230, or 240 Vac Input and Output

Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch

Table 16. Input Current - Size Overcurrent Protection According To Local Code

Voltage

Charger

500 VA

700 VA

850 VA

1.15 kVA

1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

220 Vac

Standard

2.6A

3.9A

4.4A

4.9A

5.7A

7.9A

8.2A

13A

15A

4.7A

6.0A

6.5A

7.0A

7.8A

14A

15A

19A

230 Vac

Standard

2.5A

3.8A

4.2A

4.6A

5.4A

7.5A

7.8A

12A

15A

4.6A

5.9A

6.3A

6.7A

7.5A

14A

14A

18A

240 Vac

Standard

2.4A

3.5A

4.0A

4.4A

5.2A

7.2A

7.4A

12A

15A

4.6A

5.7A

6.2A

6.6A

7.4A

14A

14A

19A

Advertising