FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

C H A P T E R

6

I

NTERNAL

B

YPASS

S

WITCH

I

NSTALLATION

W A R N I N G

Only qualified service personnel (such as a licensed electrician) should perform the
hardwired installation. Risk of electrical shock.

C A U T I O N

Before you install the bypass switch, verify that the bypass switch and the AC
disconnect switch are in the OFF position.

1. Identify the installation wiring diagram that applies to your

FERRUPS (see Table 21).

Table 21. Internal Bypass Switch Wiring Diagrams

Model (Frequency)

UPS Input Voltage

UPS Output Voltage

Bypass Switch Type

Wiring Diagram

FE 4.3–18 kVA (60 Hz)

120

(4.3–7 kVA only)

120

MBB or BBM

Figure 17 on page 49

208 or 240

120/208 or 120/240

MBB or BBM

For 208V, use BBM only

Figure 18 on page 50

208 or 480 source*/

240 input

120/240

MBB or BBM

Figure 19 on page 51

220**

220

BBM

Figure 20 on page 52

QFE 4.3–18 kVA (50 Hz)

220, 230, or 240

220, 230, or 240

MBB or BBM

Figure 20 on page 52

*With a step-up or step-down transformer.
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,
or (b) split-phase installations that require 220 Vac.