External Bypass Switch Installation

37

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.

Figure 9. FE 500 VA–3.1 kVA UPS with External Bypass Switch

Table 14. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac

208 Vac

240 Vac

Charger

500 VA –1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

500 VA –1.4 kVA

1.8 kVA

2.1 kVA

3.1 kVA

Standard

15

15

15

20

15

15

15

15

15A

15

20

25

30

15

20

20

25