49

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide

:

Rev A www.powerware.com

NOTE 10 The load fuse or circuit breaker should be sized to match the load current
requirements.

NOTE 11 For 208 Vac, use a step-up transformer For 480 Vac, use a step-down
transformer. Use an isolation transformer with a 120/240 grounded center-tapped
neutral output. Do not use a buck/boost transformer.

60 Hz 120 Vac Input - 120 Vac Output

Figure 17. FE 4.3–7 kVA UPS with Internal Bypass Switch

Table 23. Minimum Recommended Circuit Breakers for 120 Vac

Charger

4.3 kVA

5.3 kVA

7 kVA

Standard

40

50

70

10A

45

60

70

20A

50

60

70