Recommended Downstream Protection (EU Models Only)

The indicated protection ensures discrimination for each output circuit
downstream of the UPS.

If these recommendations are not followed, protection discrimination is
not achieved and may result in a potential power interruption to the
connected devices.

UPS Power Rating

Downstream Circuit Breaker

EU Models Only

5000 VA

Z curve − 10A

C curve − 4A

6000 VA

Z curve − 10A

C curve − 6A

Required Cable Cross−Sections

Function

Wiring

EU Models

U Models

Terminal block cable
capacity

6 mm

2

, solid or stranded wire

(maximum 8 mm

2

or 8 AWG).

6 mm

2

, solid or stranded wire

(maximum 8 mm

2

or

10 AWG).

Capacity for ground/
earthing conductor

Continue to the following section, Connecting the Power Cables (EU
Models)," or to Connecting the Power Cables (U Models)" on page 42.